IAQ tradeoffs with energy: ventilation has a heating bill

Every cubic foot of outside air you bring in is air you have to heat or cool. In some climates "just open windows" is correct; in others it is the most expensive intervention you can pick.

Also in: Français Español

A residential HRV unit in a basement utility room with frost on the outside vent and a Terrestream sensor on a wall.
Photo: Đỗ Huy Hoàng via Pexels
comparison-bar Interactive chart - coming soon
HVAC energy per CFM of outside air, by climate zone and season: cold winter (high), mild shoulder (low), hot/humid summer (high).

The first-order physics is unforgiving: every cubic foot per minute (CFM) of outside air you bring into a conditioned home is one CFM of conditioned air leaving, and you pay to bring the new air back to your setpoint. In a 0°F (-18°C) Minneapolis winter, raising 200 CFM of outdoor air from 0°F to 70°F costs roughly 3.0 kW of continuous heating (about $0.30 per hour at typical residential rates, or ~$200 a month if run 24/7). In a 95°F humid Atlanta summer, the same airflow is roughly 2.5 kW of cooling plus dehumidification. The ASHRAE 62.2 residential ventilation rate (3 cfm per 100 sq ft plus 7.5 cfm per occupant) for a typical 2,000 sq ft 4-person home is about 90 CFM continuous, so the real numbers are smaller than 200-CFM example, but the proportionality holds.

The energy-recovery answer is the heat-recovery ventilator (HRV) or energy-recovery ventilator (ERV). Both run two airstreams (incoming outside, outgoing inside) past each other across a thermal exchanger. DOE data shows 70-90% sensible-heat capture for modern units, which transforms the ventilation-energy math: that 3.0 kW Minneapolis winter penalty becomes 0.3-0.9 kW after recovery, roughly the cost of a couple of LED bulbs running. ERVs additionally transfer moisture (sensible + latent recovery), making them the better choice in humid climates where dehumidification load dominates.

The climate-zone-dependent recommendation: cold dry climates (zones 6-8): HRV beats open windows for sustained ventilation; window-cracking is fine in shoulder seasons but expensive mid-winter. Hot humid climates (zones 1-2): ERV beats HRV (latent recovery matters more than sensible), and open windows are a humidity disaster on most summer days. Mild marine climates (zone 4C, parts of zone 5): natural ventilation handles most of the year; mechanical ventilation only matters during heat waves and cold snaps. Mixed climates (zones 3-5): the answer is "it depends on the day", which is exactly what demand-controlled ventilation is for.

Why "just open more windows" is sometimes wrong: in a humid summer, you import moisture you then have to dehumidify; in a polluted-outdoor-air period, you import the very PM2.5 or ozone you were trying to dilute. The dashboard cross-references outdoor air feeds and humidity before recommending window-opening. When ozone is red, the recommendation auto-suppresses; when outdoor PM2.5 exceeds indoor PM2.5, the recommendation flips to "keep closed and filter". The economic case for an HRV/ERV strengthens in proportion to how often the outdoor air is unsuitable for direct intake. For envelope considerations see sealing and air tightness.

References

  1. ASHRAE Standard 62.2 - Residential ventilation www.ashrae.org
  2. DOE - Whole-house ventilation (ERV/HRV) www.energy.gov
  3. ENERGY STAR - Ventilating fans (ERV) www.energystar.gov
  4. LBNL - Residential building publications buildings.lbl.gov